Details
Specification
- Approvals: FM Approved, UL Listed
- Rated Voltage: 24VDC
- Supply Voltage: 19VDC – 33 VDC
- Supervisory Current: Emitter 50μA @ 24VDC Receiver 200μA @ 24VDC
- Alarm Current: (Receiver) 20mA @ 24DC
- Operating Temperature Range: 14° F – 122° F
- UL Installation Temperature Range: 32° F – 100° F
- Allowable misalignment angle: Emitter +/- 0.5° (MAX) Receiver +/- 1.0°
- Sensitivity Test Failure: Hochiki test filters (sold separately)
Description
The Hochiki SPC-24 Projected Beam Smoke Detector consists of an emitter and receiver. The SPC-24 detector should be placed so that smoke generated by a fire will likely rise into the path of the beam. The receiver is constantly monitoring and measuring the intensity of the beam transmitted by the emitter. Should the smoke from a fire cause a decrease in the signal strength of a magnitude that exceeds the programmed obscuration setting, an alarm signal is generated.
The SPC-24 detector can provide vital fire detection in applications where other types of detectors may not be able to respond quickly, or at all, to a fire condition. Examples of some applications where projected beam smoke detectors have been successfully used include:
Atriums gymnasiums theaters museums factories tunnels churches stables warehouses anechoic chambers high air velocity areas
The SPC-24 detector may also be used in conjunction with more traditional spot type smoke detection devices to provide an even more comprehensive detection system.