SPC-24 Projected Beam Smoke Detector

Details

Specification

  • Approvals: FM Approved, UL Listed
  • Rated Voltage: 24VDC
  • Supply Voltage: 19VDC – 33 VDC
  • Supervisory Current: Emitter 50μA @ 24VDC Receiver 200μA @ 24VDC
  • Alarm Current: (Receiver) 20mA @ 24DC
  • Operating Temperature Range: 14° F – 122° F
  • UL Installation Temperature Range: 32° F – 100° F
  • Allowable misalignment angle: Emitter +/- 0.5° (MAX) Receiver +/- 1.0°
  • Sensitivity Test Failure: Hochiki test filters (sold separately)

Description

The Hochiki SPC-24 Projected Beam Smoke Detector consists of an emitter and receiver. The SPC-24 detector should be placed so that smoke generated by a fire will likely rise into the path of the beam. The receiver is constantly monitoring and measuring the intensity of the beam transmitted by the emitter. Should the smoke from a fire cause a decrease in the signal strength of a magnitude that exceeds the programmed obscuration setting, an alarm signal is generated.
The SPC-24 detector can provide vital fire detection in applications where other types of detectors may not be able to respond quickly, or at all, to a fire condition. Examples of some applications where projected beam smoke detectors have been successfully used include:
Atriums gymnasiums theaters museums factories tunnels churches stables warehouses anechoic chambers high air velocity areas
The SPC-24 detector may also be used in conjunction with more traditional spot type smoke detection devices to provide an even more comprehensive detection system.

Features

Approvals: FM Approved, UL Listed
Microprocessor based for reliability
Provides 60 feet on center linear protection at arange of 32.8 feet to 328 feet
Automatic compensation for signal drift or dirty lens
Three field adjustable sensitivity settings
Adjustable to one of the three obscuration settings of 25%, 50% or 70% per span
Voltage and RF transient protection